 |
TECHNICAL-FLOOR
INSULATION THICKNESS
U-VALUES,
BUILDING REGULATION CHANGES AND INSULATION
|
A
ROUGH GUIDE TO AID UNDERSTANDING |
| Insulation
is required below all underfloor heating systems to stop downward heat
transmission. As well as this purpose it is also necessary under the building
regulations to provide the better-insulated buildings and reduce building
heating requirements. These requirements have recently changed.
|
| U-Values
and Building Regulations
|
Recent
changes to the building regulations have reduced the stipulated U-Value
for floors from 0.45 to 0.25 W/m²K.
The
formula for calculation of a ground floor U-Value is given in CIBSE
Guide A3 and is very complicated. A simplified method of calculating
the U-Value of an uninsulated floor has been described in BRE Information
Paper IP 3/90.
This
simplified formula can be used for all types of ground floor including;
ground bearing, suspended concrete and suspended timber. It can also
be used with relative ease for irregularly shaped floor plans, not just
simple rectangular shapes.
|
The
IP 3/90 formula is:
U
= 0.05 + 1.65(P/A) - 0.6(P/A)²
Where:
U = U-Value of the uninsulated floor (W/m²K).
P = Length of the exposed perimeter (m).
A = Area of the floor (m²)
|
Note:
The
measurement of the perimeter and area should be to the inside surface
of the perimeter walls that enclose the heated space. Unheated spaces
such as garages and porches etc. should be excluded. The perimeter should
not include walls between adjacent heated areas such as semi-detached
or terraced properties.
|
U-Values
of Uninsulated Ground Floor
The
formula yields the following values for different perimeter to area
ratios
|
Uninsulated
U-Value |
| Perimeter/Area
Ratio |
P/A
= |
0.10 |
0.1253 |
0.20 |
0.30 |
0.40 |
0.50 |
0.60 |
0.70 |
Uninsulated
U-Value |
U
= |
0.21 |
0.25 |
0.36 |
0.50 |
0.62 |
0.73 |
0.83 |
0.92 |
| The
above table shows that only floor plans with P/A ratios less than 0.1253
will meet the new building regulations without additional insulation.
Using the figures above we can calculate the effective thermal resistance
of the uninsulated floor (m²K/W) (- this is the reciprocal of the
U-Value).
In order to meet the new building regulations for a U-Value no greater
than 0.25 we must therefore increase the thermal resistance to at least
4.0 by the addition of insulation.
Knowing the additional component thermal resistance that the insulation
must provide we can then calculate the required thickness of insulation
from the thermal conductivity of the material.
The table can then be expanded to give guidelines as to what thickness
of each type of insulation is required to bring the floor U-value under
0.25.
On a cautionary note it must be stressed that the following table is based
on approximate calculations as detailed above and is for guidance only.
It is intended to help give some 'feel' for insulation requirements and
cannot replace full U-Value calculations.
The attached table provides a guide to the required floor insulation thickness
With the different types of floor insulation available.
|
Warmafloor
UK. Concorde House, Concorde Way, Segensworth North,
Fareham, Hampshire, PO15 5RL
TEL
: 01489 581787 FAX: 01489 576444
|
 |